The Main Technical Differences Between The High Voltage Generator Set And The Low Voltage Generator Set

Nov 06, 2023

Leave a message

The generator set is generally composed of engine, generator, unit integrated control system, oil circuit system and distribution system. The power part of the generator set in the communication system - diesel engine or gas turbine engine for high pressure unit and low pressure unit is basically no difference; The configuration of the oil circuit system and the amount of fuel are mainly related to the power, so there is no significant difference in the high and low pressure units, so the requirements of the unit inlet and exhaust air system that provides cooling for the unit are no difference. The difference in parameters and performance between the high voltage generator set and the low voltage generator set is mainly reflected in the generator part and the distribution system part.
1. The difference in volume and weight
High-voltage generator sets use high-voltage generators, and the improvement of voltage levels makes its insulation requirements higher, and correspondingly, the volume and weight of the generator part is larger than that of the low-voltage unit. Therefore, the volume and weight of the whole body of the 10kV generator set are slightly larger than that of the low-pressure unit. There is no major difference in appearance except for the slight difference in the generator part.
2. Differences in grounding modes
The neutral grounding modes of the two generator sets are different. The winding of the 380V unit is a star connection, and the general low-voltage system is a direct grounding system for the neutral point, so the neutral point of the star connection of the generator is set to the withdrawable type, which can be directly grounded when needed. The 10kV system is a small current grounding system, and the neutral point is generally not grounded or is grounded through the grounding resistance. Therefore, the 10kV unit needs to increase the neutral point distribution equipment such as resistance cabinet and contactor cabinet compared with the low-voltage unit.
3. Differences in protection methods
The high voltage generator set generally requires the installation of current current break protection, overload protection, grounding protection and so on. When the sensitivity of current velocity break protection does not meet the requirements, the longitudinal differential protection can be installed.
When a ground fault occurs in the operation of a high voltage generator set, it may cause a great safety hazard to the human body and the device. Therefore, it is necessary to set the ground fault protection.
The neutral point of generator is grounded through resistance. When single-phase grounding fault occurs, the fault current flowing through the neutral point can be detected, and tripping or stopping protection can be realized through relay protection. The neutral point of the generator is grounded through resistance, which can limit the fault current within the allowable damage curve of the generator, and the generator can operate with fault. Through the grounding resistance, the grounding fault can be detected effectively and the relay protection action can be driven. Compared with the low voltage unit, the high voltage generator set needs to add neutral point distribution equipment such as resistance cabinet and contactor cabinet.
The high voltage generator set should be equipped with differential protection if necessary.
Three-phase current differential protection is provided on the stator windings of the generator. The current transformer installed in the two outlet terminals of each group of coils of the generator measures the current difference between the inlet and outlet terminals of the coils to judge the coil insulation. When any two or three phases are short-circuited or grounded, the fault current can be detected in both transformers to drive protection.
4. Differences in output cables
Under the same capacity level, the outlet cable diameter of the high-voltage unit is much thinner than that of the low-voltage unit, so the space occupation requirement for the outlet channel is lower.
5. Differences in unit control systems
The unit control system of the low-pressure unit can generally be integrated on the side of the generator part of the fuselage, while the high-pressure unit takes into account the signal interference problem, generally requires an independent unit control box, which is arranged separately from the unit.
6. Differences in maintenance requirements
The maintenance requirements of the high voltage generator set in the oil circuit system and the intake and exhaust system are similar to those of the low voltage unit, but the power distribution of the unit is a high voltage system, and the maintenance personnel need to be equipped with a high voltage duty certificate.